Standby Power Battery Sizing
Constant Power Discharge Calculation Example
Constant Power Discharge Tables Previous Page Next Page
Because the YHP19 gives greater than requirement it is possible to
reduce the number of cells as follows -
 
Try 186 cells: Minimum Cell Voltage: 306 / 186 = 1.645 volts
Watts per Cell Required: 355.6 x 1000 / 186 = 1912 Watts
From the data sheets for Constant Power discharges to 1.65 volts for 15 minutes
YHP19 gives 1944 watts for 15 minutes to 1.65 volts
186 YHP19 cells therefore meet the duty.
Similarly -
Try 180 cells: Minimum Cell Voltage: 306 / 180 = 1.70 volts
Watts per Cell Required: 355.6 x 1000 / 180 = 1976 Watts
From the data sheets for Constant Power discharges to 1.70 volts for 15 minutes
YHP19 gives 1773 watts for 15 minutes to 1.70 volts
180 YHP19 cells therefore do not meet the duty!