Because
the YHP19 gives greater than requirement it is possible
to
reduce the number of cells as follows - |
| Try
186 cells: |
Minimum
Cell Voltage: 306 / 186 = 1.645 volts
Watts per Cell Required: 355.6 x 1000 / 186 = 1912 Watts |
From the
data sheets for Constant Power discharges to 1.65 volts for
15 minutes
| YHP19 |
gives
1944 watts for 15 minutes to 1.65 volts |
186 YHP19 cells therefore meet
the duty. |
|
| Try
180 cells: |
Minimum
Cell Voltage: 306 / 180 = 1.70 volts
Watts per Cell Required: 355.6 x 1000 / 180 = 1976 Watts |
From the
data sheets for Constant Power discharges to 1.70 volts for
15 minutes
| YHP19 |
gives 1773 watts for 15 minutes
to 1.70 volts |
180 YHP19 cells therefore do not meet
the duty! |
|
|