Standby Power - FHP 55 Data Printer Friendly Previous Page Temperature Correction
To view data for entire range, click here: Specifications :
Constant Current
: Constant Power

Product Specification Data
Type Nom
V
C10@
25°C
L
mm
W
mm
H
mm
Mass
kg
Acid
l
Cell
Arrangement
Cell
Centre
FHP 55 2 3540 509 368 682 225.7 60.8 E to E 394

Constant Current Discharge Data (amps at 25 °C)
Cell / Bat Type VpC 5 Min 10 Min 15 Min 20 Min 30 Min 45 Min 1 Hr 2 Hr 3 Hr 5 Hr 6 Hr 8 Hr 10 Hr
FHP 55 1.60 4370 3984 3599 3149 2699 2217 1896 1221 926 636 559 450 386
1.65 4016 3679 3309 2940 2545 2121 1813 1189 910 633 556 447 384
1.70 3615 3293 2988 2683 2362 2008 1716 1157 891 626 553 444 382
1.75 3219 2914 2641 2400 2137 1864 1588 1109 872 619 543 437 376
1.80 2818 2538 2288 2088 1896 1687 1450 1028 835 602 530 430 371
1.85 2400 2140 1953 1777 1594 1407 1207 903 764 565 498 408 354

Constant Power Discharge Data (watts at 25°C)
Cell / Bat Type VpC 5 Min 10 Min 15 Min 20 Min 30 Min 45 Min 1 Hr
FHP 55 1.60 6992 6374 5758 5038 4318 3547 3033
1.65 6627 6070 5460 4851 4199 3499 2991
1.70 6145 5599 5080 4561 4015 3414 2918
1.75 5634 5100 4622 4200 3739 3261 2778
1.80 5072 4569 4118 3759 3412 3036 2611
1.85 4440 3959 3614 3287 2948 2603 2233
© First National Battery 2004