Standby Power - FHP 35 Data Printer Friendly Previous Page Temperature Correction
To view data for entire range, click here: Specifications :
Constant Current
: Constant Power

Product Specification Data
Type Nom
V
C10@
25°C
L
mm
W
mm
H
mm
Mass
kg
Acid
l
Cell
Arrangement
Cell
Centre
FHP 35 2 2230 357 368 682 150.4 42.4 F to F 380

Constant Current Discharge Data (amps at 25 °C)
Cell / Bat Type VpC 5 Min 10 Min 15 Min 20 Min 30 Min 45 Min 1 Hr 2 Hr 3 Hr 5 Hr 6 Hr 8 Hr 10 Hr
FHP 35 1.60 2751 2508 2266 1983 1699 1396 1194 769 583 400 352 283 243
1.65 2529 2316 2084 1851 1602 1335 1141 748 573 399 350 281 242
1.70 2276 2074 1881 1689 1487 1264 1081 728 561 394 348 279 241
1.75 2027 1835 1663 1511 1345 1173 1000 698 549 390 342 275 237
1.80 1774 1598 1440 1315 1194 1062 913 647 526 379 334 271 234
1.85 1511 1347 1230 1119 1003 886 760 569 481 356 314 257 223

Constant Power Discharge Data (watts at 25°C)
Cell / Bat Type VpC 5 Min 10 Min 15 Min 20 Min 30 Min 45 Min 1 Hr
FHP 35 1.60 4402 4014 3625 3172 2719 2233 1910
1.65 4173 3822 3438 3054 2644 2203 1883
1.70 3869 3525 3198 2872 2528 2149 1837
1.75 3547 3211 2910 2645 2354 2053 1749
1.80 3194 2877 2593 2367 2148 1912 1644
1.85 2796 2493 2275 2070 1856 1639 1406
© First National Battery 2004