Standby Power - FHP 31 Data Printer Friendly Previous Page Temperature Correction
To view data for entire range, click here: Specifications :
Constant Current
: Constant Power

Product Specification Data
Type Nom
V
C10@
25°C
L
mm
W
mm
H
mm
Mass
kg
Acid
l
Cell
Arrangement
Cell
Centre
FHP 31 2 1970 306 368 682 130.6 35.2 F to F 330

Constant Current Discharge Data (amps at 25 °C)
Cell / Bat Type VpC 5 Min 10 Min 15 Min 20 Min 30 Min 45 Min 1 Hr 2 Hr 3 Hr 5 Hr 6 Hr 8 Hr 10 Hr
FHP 31 1.60 2428 2213 1999 1749 1499 1232 1053 678 514 353 311 250 214
1.65 2231 2044 1839 1633 1414 1178 1007 660 506 352 309 248 213
1.70 2008 1830 1660 1490 1312 1116 954 643 495 348 307 246 212
1.75 1789 1619 1467 1333 1187 1035 882 616 484 344 302 243 209
1.80 1565 1410 1271 1160 1053 937 806 571 464 335 294 239 206
1.85 1333 1189 1085 987 885 782 671 502 424 314 277 227 197

Constant Power Discharge Data (watts at 25°C)
Cell / Bat Type VpC 5 Min 10 Min 15 Min 20 Min 30 Min 45 Min 1 Hr
FHP 31 1.60 3884 3541 3199 2799 2399 1970 1685
1.65 3682 3372 3034 2695 2333 1944 1662
1.70 3414 3110 2822 2534 2230 1897 1621
1.75 3130 2833 2568 2333 2077 1812 1544
1.80 2818 2538 2288 2088 1896 1687 1450
1.85 2467 2199 2008 1826 1638 1446 1241
© First National Battery 2004