Standby Power - FCP 27 Data Printer Friendly Previous Page Temperature Correction
To view data for entire range, click here: Specifications :
Constant Current
: Constant Power

Product Specification Data
Type Nom
V
C10@
25°C
L
mm
W
mm
H
mm
Mass
kg
Acid
l
Cell
Arrangement
Cell
Centre
FCP 27 2 416 248 203 423 34.3 8.9 E to E 209

Constant Current Discharge Data (amps at 25 °C)
Cell / Bat Type VpC 5 Min 10 Min 15 Min 20 Min 30 Min 45 Min 1 Hr 2 Hr 3 Hr 5 Hr 6 Hr 8 Hr 10 Hr
FCP 27 1.60 594 512 479 428 313 261 208 132 99.5 69.6 61.0 49.0 41.6
1.65 554 483 435 406 313 261 208 132 99.5 69.6 61.0 49.0 41.6
1.70 469 432 397 364 313 261 208 132 99.5 69.6 61.0 49.0 41.6
1.75 398 381 347 316 278 239 208 132 99.5 69.6 61.0 49.0 41.6
1.80 320 299 288 274 242 208 177 122 99.5 69.6 61.0 49.0 41.6
1.85 262 250 230 208 195 161 145 113 92.3 67.6 59.0 49.0 41.6

Constant Power Discharge Data (watts at 25°C)
Cell / Bat Type VpC 5 Min 10 Min 15 Min 20 Min 30 Min 45 Min 1 Hr
FCP 27 1.60 968 840 795 710 526 456 372
1.65 925 811 735 690 532 456 372
1.70 802 743 683 626 545 456 372
1.75 704 674 614 559 492 425 372
1.80 576 541 521 496 440 381 326
1.85 485 463 426 385 361 299 271
© First National Battery 2004