Standby Power - T12V130 Data Printer Friendly Previous Page Temperature Correction
To view data for entire range, click here: Specifications :
Constant Current
: Constant Power

Product Specification Data
Type Nom
V
C10@
20°C
L
mm
W
mm
H
mm
Mass
kg
Acid
l
Cell
Arrangement
Cell
Centre
T12V130 12 129 548 115 275 50 - - -

Constant Current Discharge Data (amps at 20 °C)
Cell / Bat Type VpC 5 Min 10 Min 15 Min 20 Min 30 Min 45 Min 1 Hr 2 Hr 3 Hr 5 Hr 6 Hr 8 Hr 10 Hr
T12V130 1.60 - - - - 145 107 85.7 - 36.1 23.4 - 15.8 13.1
1.65 - - - - 143 106 85.2 - 35.9 23.3 - 15.7 13.1
1.70 - - - - 140 104.5 84.6 - 35.6 23.1 - 15.6 13
1.75 - - - - 133 101 82.5 - 35.3 22.9 - 15.5 13
1.80 - - - - 126 96.7 79.5 - 34.5 22.6 - 15.4 12.9
1.85 - - - - 111.5 88 72.8 - 32.7 21.9 - 14.9 12.4

Constant Power Discharge Data (watts at 20°C)
Cell / Bat Type VpC 5 Min 10 Min 15 Min 20 Min 30 Min 45 Min 1 Hr
T12V130 1.60 - - - - 1540 1175 960
1.65 - - - - 1530 1170 955
1.70 - - - - 1510 1160 950
1.75 - - - - 1470 1135 930
1.80 - - - - 1390 1090 905
1.85 - - - - 1275 1010 846
© First National Battery 2004