Standby Power - T12V35 Data Printer Friendly Previous Page Temperature Correction
To view data for entire range, click here: Specifications :
Constant Current
: Constant Power

Product Specification Data
Type Nom
V
C10@
20°C
L
mm
W
mm
H
mm
Mass
kg
Acid
l
Cell
Arrangement
Cell
Centre
T12V35 12 35 280 108 194 14.6 - - -

Constant Current Discharge Data (amps at 20 °C)
Cell / Bat Type VpC 5 Min 10 Min 15 Min 20 Min 30 Min 45 Min 1 Hr 2 Hr 3 Hr 5 Hr 6 Hr 8 Hr 10 Hr
T12V35 1.60 - - - - 40.5 30.1 24.2 - 10 6.5 - 4.4 3.6
1.65 - - - - 40 29.8 24 - 10 6.5 - 4.3 3.6
1.70 - - - - 39.3 29.3 23.6 - 9.9 6.4 - 4.3 3.5
1.75 - - - - 38.1 28.4 23.1 - 9.7 6.3 - 4.3 3.5
1.80 - - - - 36 27.3 22.3 - 9.5 6.2 - 4.2 3.5
1.85 - - - - 32.2 24.6 20.4 - 9.1 6 - 4.1 3.3

Constant Power Discharge Data (watts at 20°C)
Cell / Bat Type VpC 5 Min 10 Min 15 Min 20 Min 30 Min 45 Min 1 Hr
T12V35 1.60 - - - - 449 337 274
1.65 - - - - 443 335 272
1.70 - - - - 436 331 270
1.75 - - - - 422 324 264
1.80 - - - - 397 309 257
1.85 - - - - 353 281 234
© First National Battery 2004