Standby Power - 12 OPzV 1200 Data Printer Friendly Previous Page Temperature Correction
To view data for entire range, click here: Specifications :
Constant Current
: Constant Power

Product Specification Data
Type Nom
V
C10@
20°C
L
mm
W
mm
H
mm
Mass
kg
Acid
l
Cell
Arrangement
Cell
Centre
12 OPzV 1200 2 1200 212 277 688 94 - - -

Constant Current Discharge Data (amps at 20 °C)
Cell / Bat Type VpC 5 Min 10 Min 15 Min 20 Min 30 Min 45 Min 1 Hr 2 Hr 3 Hr 5 Hr 6 Hr 8 Hr 10 Hr
12 OPzV 1200 1.65 - 1225 1131 - 990 - 726 485 359 240 - 166 123
1.70 - 1112 1037 - 869 - 665 474 354 240 - 166 123
1.75 - 956 903 - 790 - 614 450 342 237 - 165 123
1.80 - 865 806 - 687 - 550 407 318 232 - 151 123
1.83 - 771 703 - 591 - 507 372 298 224 - 148 121
1.87 - 500 480 - 449 - 420 309 262 204 - 140 118

Constant Power Discharge Data (watts at 20°C)
Cell / Bat Type VpC 5 Min 10 Min 15 Min 20 Min 30 Min 45 Min 1 Hr
12 OPzV 1200 1.65 2187 2007 1879 1755 1599 - 1196
1.70 1932 1806 1707 1603 1460 - 1115
1.75 1761 1639 1540 1462 1322 - 1010
1.80 1536 1424 1339 1263 1125 - 889
1.83 1354 1238 1140 1063 961 - 801
1.87 1092 1000 935 881 822 - 710
© First National Battery 2004