Standby Power - 6 V 4 OPzV 200 Data Printer Friendly Previous Page Temperature Correction
To view data for entire range, click here: Specifications :
Constant Current
: Constant Power

Product Specification Data
Type Nom
V
C10@
20°C
L
mm
W
mm
H
mm
Mass
kg
Acid
l
Cell
Arrangement
Cell
Centre
6 V 4 OPzV 200 6 182 273 204 350 43 - - -

Constant Current Discharge Data (amps at 20 °C)
Cell / Bat Type VpC 5 Min 10 Min 15 Min 20 Min 30 Min 45 Min 1 Hr 2 Hr 3 Hr 5 Hr 6 Hr 8 Hr 10 Hr
6 V 4 OPzV 200 1.65 313 273 240 - 179 - 114 70.3 50.9 33.8 29 22.8 18.6
1.70 277 253 223 - 173 - 114 70.3 50.9 33.8 29 22.8 18.6
1.75 253 227 187 - 155 - 108 66.5 49.8 33.1 28.4 22.4 18.6
1.80 231 201 181 - 148 - 101 63.9 47.9 31.9 27.6 22 18.2
1.83 205 181 162 - 131 - 91.2 60 45.2 30.8 26.7 21.3 17.5
1.87 177 162 137 - 116 - 81.7 55.9 42.6 29.3 25.3 20.1 16.7

Constant Power Discharge Data (watts at 20°C)
Cell / Bat Type VpC 5 Min 10 Min 15 Min 20 Min 30 Min 45 Min 1 Hr
6 V 4 OPzV 200 1.65 1575 1386 1230 - 933 - 627
1.70 1428 1314 1170 - 918 - 627
1.75 1335 1206 999 - 834 - 597
1.80 1254 1098 993 - 816 - 567
1.83 1131 999 900 - 729 - 516
1.87 999 915 774 - 654 - 468
© First National Battery 2004