| Standby Power - 12 V 3 OPzV 150 Data | ||||
| To
view data for entire range, click here: Specifications
: Constant Current : Constant Power |
||||
| Product Specification Data | |||||||||
| Type | Nom V |
C10@ 20°C |
L mm |
W mm |
H mm |
Mass kg |
Acid l |
Cell Arrangement |
Cell Centre |
| 12 V 3 OPzV 150 | 12 | 137 | 381 | 204 | 350 | 63 | - | - | - |
| Constant Current Discharge Data (amps at 20 °C) | ||||||||||||||
| Cell / Bat Type | VpC | 5 Min | 10 Min | 15 Min | 20 Min | 30 Min | 45 Min | 1 Hr | 2 Hr | 3 Hr | 5 Hr | 6 Hr | 8 Hr | 10 Hr |
| 12 V 3 OPzV 150 | 1.65 | 243 | 216 | 190 | - | 137 | - | 86.9 | 53.6 | 38.2 | 25.4 | 21.8 | 17.1 | 14 |
| 1.70 | 219 | 198 | 176 | - | 133 | - | 86.9 | 53.6 | 38.2 | 25.4 | 21.8 | 17.1 | 14 | |
| 1.75 | 200 | 179 | 148 | - | 120 | - | 82.7 | 50.2 | 37.3 | 24.8 | 21.3 | 16.8 | 14 | |
| 1.80 | 181 | 157 | 141 | - | 110 | - | 76.9 | 47.6 | 35.9 | 23.9 | 20.7 | 16.5 | 13.7 | |
| 1.83 | 162 | 141 | 126 | - | 103 | - | 69.8 | 45.3 | 33.9 | 23.1 | 20 | 16 | 13.1 | |
| 1.87 | 139 | 126 | 108 | - | 91.8 | - | 62.7 | 42.5 | 31.9 | 21.9 | 19 | 15.1 | 12.5 | |
| Constant Power Discharge Data (watts at 20°C) | ||||||||
| Cell / Bat Type | VpC | 5 Min | 10 Min | 15 Min | 20 Min | 30 Min | 45 Min | 1 Hr |
| 12 V 3 OPzV 150 | 1.65 | 2454 | 2196 | 1944 | - | 1422 | - | 948 |
| 1.70 | 2262 | 2058 | 1848 | - | 1410 | - | 948 | |
| 1.75 | 2112 | 1902 | 1578 | - | 1296 | - | 912 | |
| 1.80 | 1968 | 1716 | 1548 | - | 1212 | - | 864 | |
| 1.83 | 1788 | 1554 | 1398 | - | 1146 | - | 786 | |
| 1.87 | 1566 | 1422 | 1218 | - | 1032 | - | 720 | |
| © First National Battery 2004 |