Standby Power - A412/180 A Data Printer Friendly Previous Page Temperature Correction
To view data for entire range, click here: Specifications :
Constant Current
: Constant Power

Product Specification Data
Type Nom
V
C10@
20°C
L
mm
W
mm
H
mm
Mass
kg
Acid
l
Cell
Arrangement
Cell
Centre
A412/180 A 12 180 518 274 238 69.5 - - -

Constant Current Discharge Data (amps at 20 °C)
Cell / Bat Type VpC 5 Min 10 Min 15 Min 20 Min 30 Min 45 Min 1 Hr 2 Hr 3 Hr 5 Hr 6 Hr 8 Hr 10 Hr
A412/180 A 1.60 439 322 258 217 162 123 96 64 46.1 - - - -
1.65 399 305 250 212 159 122 96 64 46 - - - -
1.70 366 287 234 199 156 120 95 64 46 30.4 - 20.2 18
1.75 329 266 216 185 152 117 94 63 45.6 30.2 - 20.2 18
1.80 291 235 195 171 144 112 90 62 44.7 29.7 - 19.9 18
1.85 240 193 170 156 130 103 84 59 42.6 28.6 - 19.2 16.5

Constant Power Discharge Data (watts at 20°C)
Cell / Bat Type VpC 5 Min 10 Min 15 Min 20 Min 30 Min 45 Min 1 Hr
A412/180 A 1.60 4832 3701 3130 2599 1994 1484 1204
1.65 4628 3589 3074 2565 1978 1475 1198
1.70 4298 3477 2976 2503 1945 1455 1185
1.75 3950 3316 2821 2399 1876 1414 1157
1.80 3559 3012 2595 2241 1756 1339 1105
1.85 3112 2679 2284 2011 1563 1215 1016
© First National Battery 2004