| Standby Power - A412/120 A Data | ||||
| To
view data for entire range, click here: Specifications
: Constant Current : Constant Power |
||||
| Product Specification Data | |||||||||
| Type | Nom V |
C10@ 20°C |
L mm |
W mm |
H mm |
Mass kg |
Acid l |
Cell Arrangement |
Cell Centre |
| A412/120 A | 12 | 120 | 513 | 223 | 223 | 48 | - | - | - |
| Constant Current Discharge Data (amps at 20 °C) | ||||||||||||||
| Cell / Bat Type | VpC | 5 Min | 10 Min | 15 Min | 20 Min | 30 Min | 45 Min | 1 Hr | 2 Hr | 3 Hr | 5 Hr | 6 Hr | 8 Hr | 10 Hr |
| A412/120 A | 1.60 | 333 | 228 | 175 | 146 | 112 | 91 | 71 | 41 | 29.5 | - | - | - | - |
| 1.65 | 311 | 217 | 169 | 142 | 111 | 91 | 71 | 41 | 29.4 | - | - | - | - | |
| 1.70 | 280 | 200 | 160 | 136 | 109 | 90 | 70 | 40 | 29.3 | 19.6 | - | 13.2 | 12 | |
| 1.75 | 233 | 174 | 145 | 127 | 106 | 88 | 69 | 40 | 29.1 | 19.5 | - | 13.2 | 12 | |
| 1.80 | 202 | 155 | 133 | 119 | 102 | 85 | 67 | 39 | 28.7 | 19.4 | - | 13.2 | 12 | |
| 1.85 | 175 | 138 | 120 | 108 | 95 | 78 | 61 | 37 | 27.5 | 18.9 | - | 13 | 11.3 | |
| Constant Power Discharge Data (watts at 20°C) | ||||||||
| Cell / Bat Type | VpC | 5 Min | 10 Min | 15 Min | 20 Min | 30 Min | 45 Min | 1 Hr |
| A412/120 A | 1.60 | 3330 | 2260 | 1791 | 1494 | 1210 | 1014 | 847 |
| 1.65 | 3170 | 2194 | 1757 | 1474 | 1205 | 1012 | 845 | |
| 1.70 | 2938 | 2090 | 1699 | 1441 | 1195 | 1008 | 840 | |
| 1.75 | 2593 | 1940 | 1610 | 1387 | 1176 | 997 | 829 | |
| 1.80 | 2286 | 1769 | 1496 | 1346 | 1146 | 971 | 802 | |
| 1.85 | 1964 | 1575 | 1385 | 1272 | 1109 | 914 | 745 | |
| © First National Battery 2004 |