| Standby Power - A412/65 G6 Data | ||||
| To
view data for entire range, click here: Specifications
: Constant Current : Constant Power |
||||
| Product Specification Data | |||||||||
| Type | Nom V |
C10@ 20°C |
L mm |
W mm |
H mm |
Mass kg |
Acid l |
Cell Arrangement |
Cell Centre |
| A412/65 G6 | 12 | 65 | 353 | 175 | 190 | 24.6 | - | - | - |
| Constant Current Discharge Data (amps at 20 °C) | ||||||||||||||
| Cell / Bat Type | VpC | 5 Min | 10 Min | 15 Min | 20 Min | 30 Min | 45 Min | 1 Hr | 2 Hr | 3 Hr | 5 Hr | 6 Hr | 8 Hr | 10 Hr |
| A412/65 G6 | 1.60 | 170 | 116 | 92 | 76 | 58 | 49 | 42 | 24 | 17.3 | - | - | - | - |
| 1.65 | 161 | 114 | 91 | 75 | 57 | 49 | 42 | 24 | 17.3 | - | - | - | - | |
| 1.70 | 148 | 111 | 89 | 73 | 57 | 49 | 41 | 24 | 17.3 | 11.5 | - | 7.7 | 6.5 | |
| 1.75 | 134 | 107 | 84 | 70 | 56 | 48 | 41 | 24 | 17.1 | 11.4 | - | 7.7 | 6.5 | |
| 1.80 | 120 | 95 | 76 | 64 | 52 | 45 | 39 | 23 | 16.7 | 11.3 | - | 7.6 | 6.5 | |
| 1.85 | 102 | 77 | 63 | 56 | 48 | 42 | 36 | 22 | 15.9 | 10.9 | - | 7.3 | 6.2 | |
| Constant Power Discharge Data (watts at 20°C) | ||||||||
| Cell / Bat Type | VpC | 5 Min | 10 Min | 15 Min | 20 Min | 30 Min | 45 Min | 1 Hr |
| A412/65 G6 | 1.60 | 1962 | 1400 | 1137 | 940 | 729 | 547 | 440 |
| 1.65 | 1874 | 1371 | 1125 | 932 | 727 | 545 | 439 | |
| 1.70 | 1762 | 1323 | 1100 | 916 | 723 | 541 | 437 | |
| 1.75 | 1620 | 1268 | 1054 | 886 | 714 | 534 | 432 | |
| 1.80 | 1430 | 1158 | 977 | 834 | 690 | 516 | 420 | |
| 1.85 | 1221 | 1025 | 867 | 759 | 635 | 482 | 396 | |
| © First National Battery 2004 |