Standby Power - A412/32 F10 Data Printer Friendly Previous Page Temperature Correction
To view data for entire range, click here: Specifications :
Constant Current
: Constant Power

Product Specification Data
Type Nom
V
C10@
20°C
L
mm
W
mm
H
mm
Mass
kg
Acid
l
Cell
Arrangement
Cell
Centre
A412/32 F10 12 32 210 175 181 14.1 - - -

Constant Current Discharge Data (amps at 20 °C)
Cell / Bat Type VpC 5 Min 10 Min 15 Min 20 Min 30 Min 45 Min 1 Hr 2 Hr 3 Hr 5 Hr 6 Hr 8 Hr 10 Hr
A412/32 F10 1.60 101 68 54 44 33 25 20 12 8.9 - - - -
1.65 94 65 52 43 33 25 20 12 8.9 - - - -
1.70 84 60 50 42 32 25 20 12 8.9 5.8 - 3.9 3.2
1.75 73 57 46 39 31 24 19 12 8.8 5.8 - 3.9 3.2
1.80 63 51 42 36 30 23 19 12 8.6 5.7 - 3.9 3.2
1.85 53 43 36 32 28 21 17 11 8.1 5.4 - 3.7 3

Constant Power Discharge Data (watts at 20°C)
Cell / Bat Type VpC 5 Min 10 Min 15 Min 20 Min 30 Min 45 Min 1 Hr
A412/32 F10 1.60 952 687 565 469 366 276 223
1.65 916 667 554 462 362 273 221
1.70 861 639 537 450 358 269 219
1.75 776 613 509 431 350 263 215
1.80 677 562 468 403 332 252 207
1.85 580 483 414 366 304 234 194
© First National Battery 2004