Standby Power - A412/8.5 SR Data Printer Friendly Previous Page Temperature Correction
To view data for entire range, click here: Specifications :
Constant Current
: Constant Power

Product Specification Data
Type Nom
V
C10@
20°C
L
mm
W
mm
H
mm
Mass
kg
Acid
l
Cell
Arrangement
Cell
Centre
A412/8.5 SR 12 8.5 152 98 98.4 3.6 - - -

Constant Current Discharge Data (amps at 20 °C)
Cell / Bat Type VpC 5 Min 10 Min 15 Min 20 Min 30 Min 45 Min 1 Hr 2 Hr 3 Hr 5 Hr 6 Hr 8 Hr 10 Hr
A412/8.5 SR 1.60 24 16 13 10 7.8 6 4.8 3 2.2 - - - -
1.65 23 16 12 10 7.7 6 4.7 3 2.2 - - - -
1.70 21 15 12 10 7.6 5.9 4.7 3 2.2 1.5 - 1 0.8
1.75 19 15 12 10 7.5 5.8 4.6 3 2.2 1.5 - 1 0.8
1.80 17 14 11 9 7.4 5.7 4.5 2.9 2.1 1.4 - 1 0.8
1.85 15 12 10 8 6.9 5.3 4.3 2.8 2.1 1.4 - 1 0.8

Constant Power Discharge Data (watts at 20°C)
Cell / Bat Type VpC 5 Min 10 Min 15 Min 20 Min 30 Min 45 Min 1 Hr
A412/8.5 SR 1.60 267 187 148 123 97 72 59
1.65 258 183 146 122 96 72 59
1.70 246 178 143 120 95 72 58
1.75 226 171 138 116 94 71 58
1.80 204 156 130 111 90 69 56
1.85 176 141 117 102 84 65 54
© First National Battery 2004