Standby Power - A406/165 F10 Data Printer Friendly Previous Page Temperature Correction
To view data for entire range, click here: Specifications :
Constant Current
: Constant Power

Product Specification Data
Type Nom
V
C10@
20°C
L
mm
W
mm
H
mm
Mass
kg
Acid
l
Cell
Arrangement
Cell
Centre
A406/165 F10 6 165 190 244 282 31.5 - - -

Constant Current Discharge Data (amps at 20 °C)
Cell / Bat Type VpC 5 Min 10 Min 15 Min 20 Min 30 Min 45 Min 1 Hr 2 Hr 3 Hr 5 Hr 6 Hr 8 Hr 10 Hr
A406/165 F10 1.60 422 318 256 215 160 122 96 59 44 - - - -
1.65 389 301 248 210 157 121 95.1 59 43.9 - - - -
1.70 332 273 233 198 152 119 94 58 44 28.7 - 19.1 16.6
1.75 290 246 210 180 143 115 92 58 43.7 28.6 - 19.1 16.6
1.80 243 211 180 158 132 109 88 56 43.1 28.2 - 18.8 16.5
1.85 196 163 143 131 115 98 82 53 41 27 - 18.1 15.9

Constant Power Discharge Data (watts at 20°C)
Cell / Bat Type VpC 5 Min 10 Min 15 Min 20 Min 30 Min 45 Min 1 Hr
A406/165 F10 1.60 1987 1588 1308 1086 836 646 527
1.65 1879 1527 1278 1067 828 643 525
1.70 1778 1455 1230 1036 814 637 522
1.75 1629 1356 1146 981 797 623 512
1.80 1414 1184 1020 901 769 596 494
1.85 1171 1005 875 798 690 543 459
© First National Battery 2004