Standby Power - 6 OPzV 420 Data Printer Friendly Previous Page Temperature Correction
To view data for entire range, click here: Specifications :
Constant Current
: Constant Power

Product Specification Data
Type Nom
V
C10@
20°C
L
mm
W
mm
H
mm
Mass
kg
Acid
l
Cell
Arrangement
Cell
Centre
6 OPzV 420 2 420 147 208 513 35 - - -

Constant Current Discharge Data (amps at 20 °C)
Cell / Bat Type VpC 5 Min 10 Min 15 Min 20 Min 30 Min 45 Min 1 Hr 2 Hr 3 Hr 5 Hr 6 Hr 8 Hr 10 Hr
6 OPzV 420 1.65 - 557 496 - 406 - 268 175 130 87 - 61 45
1.70 - 493 449 - 371 - 258 172 129 87 - 61 45
1.75 - 438 417 - 330 - 245 167 126 86 - 60 45
1.80 - 409 370 - 292 - 225 156 120 85 - 55 45
1.83 - 359 320 - 267 - 209 147 114 82 - 54 44
1.87 - 261 244 - 215 - 176 124 100 75 - 52 42

Constant Power Discharge Data (watts at 20°C)
Cell / Bat Type VpC 5 Min 10 Min 15 Min 20 Min 30 Min 45 Min 1 Hr
6 OPzV 420 1.65 938 852 788 731 617 - 425
1.70 866 786 727 671 567 - 411
1.75 754 698 630 578 494 - 391
1.80 687 602 545 502 451 - 375
1.83 578 539 476 454 417 - 354
1.87 488 457 426 404 381 - 312
© First National Battery 2004