| Standby Power - 6 OPzV 300 Data | ||||
| To
view data for entire range, click here: Specifications
: Constant Current : Constant Power |
||||
| Product Specification Data | |||||||||
| Type | Nom V |
C10@ 20°C |
L mm |
W mm |
H mm |
Mass kg |
Acid l |
Cell Arrangement |
Cell Centre |
| 6 OPzV 300 | 2 | 300 | 147 | 208 | 398 | 27 | - | - | - |
| Constant Current Discharge Data (amps at 20 °C) | ||||||||||||||
| Cell / Bat Type | VpC | 5 Min | 10 Min | 15 Min | 20 Min | 30 Min | 45 Min | 1 Hr | 2 Hr | 3 Hr | 5 Hr | 6 Hr | 8 Hr | 10 Hr |
| 6 OPzV 300 | 1.65 | - | 455 | 395 | - | 304 | - | 187 | 119 | 88 | 59 | - | 40 | 31 |
| 1.70 | - | 414 | 365 | - | 293 | - | 186 | 119 | 88 | 59 | - | 40 | 31 | |
| 1.75 | - | 362 | 344 | - | 256 | - | 182 | 118 | 87 | 58 | - | 40 | 31 | |
| 1.80 | - | 332 | 298 | - | 230 | - | 170 | 114 | 85 | 57 | - | 38 | 31 | |
| 1.83 | - | 292 | 259 | - | 217 | - | 158 | 109 | 82 | 56 | - | 37 | 31 | |
| 1.87 | - | 235 | 222 | - | 192 | - | 143 | 98 | 76 | 52 | - | 36 | 30 | |
| Constant Power Discharge Data (watts at 20°C) | ||||||||
| Cell / Bat Type | VpC | 5 Min | 10 Min | 15 Min | 20 Min | 30 Min | 45 Min | 1 Hr |
| 6 OPzV 300 | 1.65 | 816 | 728 | 668 | 600 | 517 | - | 354 |
| 1.70 | 734 | 674 | 613 | 560 | 488 | - | 349 | |
| 1.75 | 675 | 611 | 556 | 517 | 446 | - | 334 | |
| 1.80 | 599 | 538 | 497 | 456 | 397 | - | 311 | |
| 1.83 | 536 | 497 | 445 | 412 | 369 | - | 293 | |
| 1.87 | 461 | 412 | 382 | 359 | 335 | - | 264 | |